Trane Furnace 8 flashes
What this problem usually means
On Trane single-stage furnaces (XR80, XR90, XR95, XB80, XB90 families) with the integrated furnace control (IFC), the red LED flashes this count: low flame sense signal — flame is present but the flame sensor signal is too weak for reliable operation.
Likely causes
- Dirty or oxidized flame sensor
- Poor burner ground
- Weak flame from dirty burners or low gas pressure
How to fix it — step by step
- Replace the air filter and confirm all registers are open
- Reset power once and observe whether the furnace completes a full heat cycle
- Note if the furnace lights then shuts off after a few seconds — a classic weak flame-signal pattern
- Call a technician to clean or replace the flame sensor and check burner ground; sensor cleaning is burner-compartment work
Parts that commonly fix it
- flame sensor - Shop at RepairClinic
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.